Production Description:For fixed installation in conduits on or under plaster. Suitable for protected installation in and on lighting facilities or control devices for voltages up to 750 V AC or 1,000 V DC against ground.Technical Data:Standard:adapted to HD 21.3 EN 50525-2-31Rated voltage: 450/750 ......
Standard:
adapted to HD 21.3 EN 50525-2-31
Rated voltage: 450/750 V
Test voltage: 2.5 kV/50 Hz
Temperature range:
laying temperature: min. +5 °C
operating temperature: -5 °C up to +70 °C
conductor temperature: max. +70 °C
short-circuit temperature: max. +160 °C/5s
Bending radius (min.): 5 x ∅ 25 up to 50 mm2, 6 x ∅ above 50 mm2
Core identification:
green/yellow (gn/ye), black (bk), blue (bu), brown (bn), red (rd) and other colours on request
Fire properties: flame retardant: EN 60332-1-2
Certificate: EVPÚ Slovak Republic, LCIE France
Nominal cross section (mm²) | Max. conductor resistance (/km) | Outer diameter (mm) ca. | Total weight (kg/km) ca. | Standard lengths |
25 | 1.200 | 8.6 | 110 | 500D,1000D |
35 | 0.868 | 9.6 | 150 | 500D,1000D |
50 | 0.641 | 11.4 | 190 | 500D,1000D |
70 | 0.443 | 12.9 | 270 | 500D,1000D |
95 | 0.320 | 15.0 | 365 | 500D,1000D |
120 | 0.253 | 17.1 | 450 | 500D,1000D |
150 | 0.206 | 16.4 | 545 | 500D,1000D |
185 | 0.164 | 18.1 | 670 | 500D,1000D |
240 | 0.129 | 27.2 | 880 | 500D,1000D |
300 | 0.100 | 26.8 | 1090 | 500D,1000D |